APPENDIX – XIV
PER CAPITA WATER REQUIREMENT OF VARIOUS OCCUPANCIES /USES ( REGULATION NO. 5.19 )
|
PER CAPITA WATER REQUIREMENT
|
|
Sr.No.
|
Type of Occupancy
|
Consumption. In Litres per capita per day (Lpcd)
|
|
1.
|
RESIDENTIAL
|
|
|
|
(a) In living unit located on plots less than 50 sqm. In area
|
90
|
|
|
(b) In other living units
|
135
|
|
|
(c) Hotels with Lodging accommodation (per Bed)
|
180
|
|
2.
|
EDUCATIONAL
|
|
|
|
(a) Day Schools
|
45
|
|
|
(b) Boarding Schools
|
135
|
|
3.
|
INSTITUTIONAL ( Hospitals)
|
|
|
|
(a) No. of beds not exceeding 100
|
340
|
|
|
(b) No. of beds exceeding 100
|
450
|
|
|
(c) Staff quarters and hostels
|
135
|
|
4.
|
Cinema theatres, auditoria etc. (per seat of accommodation)
|
15
|
|
5.
|
Government or semi-public business offices
|
45
|
|
6.
|
Mercantile use
|
|
|
|
(a) Restaurants (per seat)
|
70
|
|
|
(b) Other business buildings
|
45
|
|
7.
|
INDUSTRIAL
|
|
|
|
(a) Factories where bath rooms are to be provided
|
45
|
|
|
(b) Factories where no bath rooms are required to be provided.
|
30
|
|
8.
|
Storage including warehousing
|
30
|
|
9.
|
Hazardous building
|
30
|
|
10.
|
Intermediate / stations (Excluding mail & Express Stops)
|
45 (25)
|
|
11.
|
Junction stations
|
70 (45)
|
|
12.
|
Terminal / stations
|
45
|
|
13.
|
International and domestic airports
|
70
|
|
|
The values in parenthesis are for stations where bathing facilities are not provided.
NOTE:-
(1) The number of persons for Sr.No. (10) to (13) shall be determined by the average number of passengers handled by the station daily. Due consideration may also be given to the staff and workers likely to use the facilities.
(2) As regards the requirement of water for cattle sheds, the norm prescribed by the Animal Husbandry and Dairy Development Department shall be followed.
FLUSHING STORAGE CAPACITIES
|
|
Sr.No.
(1)
|
CLASIFICATION OF BUILDINGS
(2)
|
STORAGE CAPACITY
(3)
|
|
1.
|
For tenements having common convenience.
|
900 litres per WC Seat.
|
|
2.
|
For residential premises other than tenements having common convenience.
|
270 litres for one WC Seat & 180 litres for each additional seat in the same flat.
|
|
3.
|
For factories and work shops.
|
900 litres per WC seat and 180 litres per urinal seat.
|
|
4.
|
For cinemas, public assembly halls etc.
|
900 litres per WC seat & 350 litres per urinal seat.
|
|
DOMESTIC STORAGE CAPACITIES
|
|
Sr.No.
|
No. of floors
|
Storage capacity
|
Remarks
|
|
I For premises occupied as Tenements with Common conveniences.
|
|
1
|
Floor 1 (Ground)
|
Nil
|
Provided no downtake fittings are
|
|
2
|
Floors 2,3,4,5 and upper floors
|
500*litres per tenement
|
|
|
II For premises occupied as Flats
|
|
1
|
Floor 1
|
Nil
|
Provided no downtake fittings are installed.
|
|
2
|
Floor 2,3,4,5 and upper floors
|
500* litres per tenement
|
|
|
|
NOTE: 1 - If the premises are situated at a place higher than the road level in front of the premises, storage at ground level shall be provided on the same lines as on floor 2.
NOTE: 2 - The above storage may be permitted to be installed provided, that the total domestic storage calculated on the above basis is not less than the storage calculated on the number of downtake fittings according to the scales given below.
Downtake taps 70 litres each
Showers 135 litres each
Bathtubs 200 litres each
* Subject to provisions of Water Supply and Drainage rules.
|
| |
|